SolaHD (Sola Hevi-Duty)
SDN2024480CD480W 24V DIN P/S 380/480V IN
480W 24V DIN P/S 380/480V IN
Single-channel AC/DC power supply unit (SMPS PSU) / converter - Emerson / SolaHD Sola/Hevi-Duty (SDN-C series) - 480W 24V DIN P/S 380/480V IN - Class I Zone 2 - 20A / 24Vdc / 480W output - 3-phase (3AC) or Single-phase (1AC) or DC input (380Vac-480Vac (400Vac / 415Vac / 440Vac nom.; 50/60Hz) / 550-650Vdc (600Vdc nom.)) - screw connections - DIN rail mounting (87mm width) - IP20 - metal housing - equivalent to SDN-2024-480CD
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
SDN2024480CD
Online Price
$788.20
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
SDN2024480CDEmerson / SolaHD - SDN-C series
Description
Single-channel AC/DC power supply unit (SMPS PSU) / converter - Emerson / SolaHD Sola/Hevi-Duty (SDN-C series) - 480W 24V DIN P/S 380/480V IN - Class I Zone 2 - 20A / 24Vdc / 480W output - 3-phase (3AC) or Single-phase (1AC) or DC input (380Vac-480Vac (400Vac / 415Vac / 440Vac nom.; 50/60Hz) / 550-650Vdc (600Vdc nom.)) - screw connections - DIN rail mounting (87mm width) - IP20 - metal housing - equivalent to SDN-2024-480CD
Additional Information
Regulated switch mode power supply unit (SMPS PSU) - Sola Hevi-Duti / Sola HD (SDN-C Performance DIN Rail Series) - Input voltage: 320Vac - 540Vac (380Vac - 480Vac nom.) (3-phase input) - Output voltage 24Vdc - Rated current 20A - Rated power 480W - rated for -40C...+60C ambiant
Specifications
Primary brand
Emerson
Secondary brand
SolaHD Sola/Hevi-Duty
Main function
Power supply unit
Product series / family name
SDN-C series
Functions
Single-channel AC/DC power supply unit (SMPS PSU) / converter
Cooling -- Convection
Status indicator -- NO contact relay (200mA; 50Vdc)
Status indicator -- Signal Active when Vout>18.5Vdc +/-5%
Cooling -- Convection
Status indicator -- NO contact relay (200mA; 50Vdc)
Status indicator -- Signal Active when Vout>18.5Vdc +/-5%
Supply voltage (AC)
380Vac-480Vac (400Vac / 415Vac / 440Vac nom.; 50/60Hz)
320Vac-540Vac
320Vac-540Vac
Supply voltage (DC)
550-650Vdc (600Vdc nom.)
Display
Input status LED
Output status LED
Alarm status LED
Output status LED
Alarm status LED
Type of network
3-phase (3AC)
Single-phase (1AC)
DC
Single-phase (1AC)
DC
Rated current
20A output (adjustable)
Rated power
480W output
Output voltage (DC)
24Vdc output (adjustable)
23.5-28.5Vdc (24Vdc nom.)
23.5-28.5Vdc (24Vdc nom.)
Connection type
screw connections
Cross-section
1.5...6mm2 / 16AWG...10AWG (screw connections; input/output)
Protection functions
Short-circuit protection -- Output automatically goes to near zero / protected from continuous Short-circuit protection -- Auto-recovery
Peak Current Protection -- 1.5 x Nominal Current for > 4 seconds minimum while holding voltage > 20Vdc
Overcurrent protection -- PowerBoostTM
Overvoltage protection -- > 30.5Vdc but < 33Vdc; auto-recovery
Over-temperature protection -- LED Alarm and Output shutdown; auto-recovery
Back EMF Immunity -- < 35V No damage; auto-recovery
Parallel operation -- Single or Parallel operation selectable via front switch.
Peak Current Protection -- 1.5 x Nominal Current for > 4 seconds minimum while holding voltage > 20Vdc
Overcurrent protection -- PowerBoostTM
Overvoltage protection -- > 30.5Vdc but < 33Vdc; auto-recovery
Over-temperature protection -- LED Alarm and Output shutdown; auto-recovery
Back EMF Immunity -- < 35V No damage; auto-recovery
Parallel operation -- Single or Parallel operation selectable via front switch.
Communication protocol
No communication interface
Mounting mode
DIN rail mounting
DIN rail TS35/7.5
DIN rail TS35/15
DIN rail TS35/7.5
DIN rail TS35/15
Degree of protection
IP20
Net Height (mm)
123 mm
Net Width (mm)
87 mm
Net Depth (mm)
127 mm
Material
metal housing
Ambient air temperature for operation
-40...+60 °C
(linear derating to 75% power) +60...+70 °C
(linear derating to 75% power) +60...+70 °C
Ambient air temperature for storage
-40...+85 °C
Manufacturer product status
Commercialized
Equivalent to
SDN-2024-480CD
Compliant with standard(s)
ATEX Directive (EN60079-0; EN60079-7; EN60079-15; II 3 G; Ex ec nC IIC Gc)
IECEx Certified IEC 60079-0; IEC 60079-7; IEC 60079-15 / Ex ec nC IIC Gc
CE marking (IEC/EN 60950-1 2nd edition)
cRUus UL recognized component (ITE - UL 60950-1/CSA C22.2 No. 60950-1 2nd Edition)
UL Recognized Component Class I Div 2; Class I Zone 2; T4
cRUus UL Recognized Component (Haz. Loc.; UL60079-0/CSA E60079-0; UL 60079-15 CSA / Class I; Zone 2; AEx nA nC IIC; Ex nA nC IIC)
cULus Listed (Ind. Control Equipment - UL 508; CSA C22.2 No. 107.1)
IEC 60068-2-27 - Shock resistance - 11ms (10G); 3 axes
IEC 60068-2-6 - Vibration resistance - 10-2000Hz; 2.5G (random) for 20mins for each axis
IECEx Certified IEC 60079-0; IEC 60079-7; IEC 60079-15 / Ex ec nC IIC Gc
CE marking (IEC/EN 60950-1 2nd edition)
cRUus UL recognized component (ITE - UL 60950-1/CSA C22.2 No. 60950-1 2nd Edition)
UL Recognized Component Class I Div 2; Class I Zone 2; T4
cRUus UL Recognized Component (Haz. Loc.; UL60079-0/CSA E60079-0; UL 60079-15 CSA / Class I; Zone 2; AEx nA nC IIC; Ex nA nC IIC)
cULus Listed (Ind. Control Equipment - UL 508; CSA C22.2 No. 107.1)
IEC 60068-2-27 - Shock resistance - 11ms (10G); 3 axes
IEC 60068-2-6 - Vibration resistance - 10-2000Hz; 2.5G (random) for 20mins for each axis
Class
Class I Zone 2
Benefits
Extensive international hazardous location certifications; including Class I; Zone 2; ATEX; IECEx; ExEAC
Hazardous location temperature code (T-Code) rating of T4
International off-shore certifications; including ABS and DNV-GL
PowerBoostTM enables short duration overload capability to start loads with high inrush current
Three LEDs provide extensive diagnostics
Dual output terminals for convenience in wiring
DC OK relay to provide diagnostic information to a PLC; controller or monitoring system
Universal AC and DC input voltages to accommodate global requirements
Wide operating temperature range accommodates both extremely hot and extremely cold environments
Active Power factor correction on most models
Parallel operation capability standard
Supports redundant power supply operation using optional SDN Redundancy modules
5-year limited warranty
Hazardous location temperature code (T-Code) rating of T4
International off-shore certifications; including ABS and DNV-GL
PowerBoostTM enables short duration overload capability to start loads with high inrush current
Three LEDs provide extensive diagnostics
Dual output terminals for convenience in wiring
DC OK relay to provide diagnostic information to a PLC; controller or monitoring system
Universal AC and DC input voltages to accommodate global requirements
Wide operating temperature range accommodates both extremely hot and extremely cold environments
Active Power factor correction on most models
Parallel operation capability standard
Supports redundant power supply operation using optional SDN Redundancy modules
5-year limited warranty
Tightening torque
(input) 0.5 N.m
(output) 0.8 N.m
(output) 0.8 N.m
Degree of pollution
2
Ripple
100mVpp max.
Application type
Altitude -- 0-3000m (0 to 10000ft)
Industrial automation
Process control
Material handling and conveyors
Hazardous locations
Marine applications
Industrial automation
Process control
Material handling and conveyors
Hazardous locations
Marine applications
MTBF (Mean Time Between Failures)
>630 000h (380Vac; at 25°C)
>630 000h (480Vac; at 25°C)
>460 000h (380Vac; at 40°C)
>450 000h (480Vac; at 40°C)
>630 000h (480Vac; at 25°C)
>460 000h (380Vac; at 40°C)
>450 000h (480Vac; at 40°C)
Related Documents
Name | Last Update | Language |
---|---|---|
SolaHD - SDN-C series - Catalog.pdf | 30 Jan 2022 | English (US) |