Pilz
PILZ-787588PZE X4.1P C 24-240Vac/DC 4N/O
PZE X4.1P C 24-240Vac/DC 4N/O
Single or dual-channel safety relay contact expansion module - SIL3 / PL.e / Cat.4 - Pilz (PNOZ X PZE X4.1P) - PZE X4.1P C 24-240Vac/DC 4N/O - 20.4-264Vdc (24Vdc / 110Vdc / 120Vdc / 220Vdc / 250Vdc nom.) / 20.4-264Vac (24Vac / 120Vac / 240Vac nom.) supp. voltage - 2 x digital inputs (24Vdc; 35mA) (K1-U-K2) + 4 x instantaneous safety outputs (4NO / 4xSPST-NO each made of 2 N.O. contacts in series; 6A 24Vdc DC-1 or 240Vac AC-1 resistive load) (13-14; 23-24; 33-34; 43-44) - plug-in/detachable spring term. connections - DIN rail mounting (W22.5mm) - IP40 - rated for -10...+55°C ambient
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
PILZ-787588
Online Price
$276.26
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Pilz - PNOZ X / PZE X4.1PPILZ-787588
Description
Single or dual-channel safety relay contact expansion module - SIL3 / PL.e / Cat.4 - Pilz (PNOZ X PZE X4.1P) - PZE X4.1P C 24-240Vac/DC 4N/O - 20.4-264Vdc (24Vdc / 110Vdc / 120Vdc / 220Vdc / 250Vdc nom.) / 20.4-264Vac (24Vac / 120Vac / 240Vac nom.) supp. voltage - 2 x digital inputs (24Vdc; 35mA) (K1-U-K2) + 4 x instantaneous safety outputs (4NO / 4xSPST-NO each made of 2 N.O. contacts in series; 6A 24Vdc DC-1 or 240Vac AC-1 resistive load) (13-14; 23-24; 33-34; 43-44) - plug-in/detachable spring term. connections - DIN rail mounting (W22.5mm) - IP40 - rated for -10...+55°C ambient
Specifications
Primary brand
Pilz
Main function
Safety relay
Product series / family name
PNOZ X
Sub-range name
PZE X4.1P
Functions
Single or dual-channel safety relay contact expansion module
Instantaneous contact expansion
Light beam device monitoring type 2 (with or without test pulse) & type 4
Instantaneous contact expansion
Light beam device monitoring type 2 (with or without test pulse) & type 4
Supply voltage (AC)
20.4-264Vac (24Vac / 120Vac / 240Vac nom.)
Supply voltage (DC)
20.4-264Vdc (24Vdc / 110Vdc / 120Vdc / 220Vdc / 250Vdc nom.)
Display
Power LED indicator
CH.1 LED indicator
CH.2 LED indicator
CH.1 LED indicator
CH.2 LED indicator
Rated current
Safety output contacts ratings
6A (24Vdc; DC-1)
6A (240Vac; AC-1)
4A (24Vdc; DC-13)
3A (230Vac; AC-15)
6A (24Vdc; DC-1)
6A (240Vac; AC-1)
4A (24Vdc; DC-13)
3A (230Vac; AC-15)
Connection type
plug-in/detachable spring term. connections
Mounting mode
DIN rail mounting
Operating mode
Single-channel / Dual-channel
Digital inputs
2 x digital inputs (24Vdc; 35mA) (K1-U-K2)
1 x feedback loop input (SPST with 2NC contacts in series) (Y1-Y2)
1 x feedback loop input (SPST with 2NC contacts in series) (Y1-Y2)
Digital outputs
4 x instantaneous safety outputs (4NO / 4xSPST-NO each made of 2 N.O. contacts in series; 6A 24Vdc DC-1 or 240Vac AC-1 resistive load) (13-14; 23-24; 33-34; 43-44)
Degree of protection
IP40
Dimensions
W22.5mm
Net Height (mm)
101 mm
Net Width (mm)
22.5 mm
Net Depth (mm)
121 mm
Material
PPO housing
ABS front housing
ABS front housing
Ambient air temperature for operation
-10...+55 °C
Power consumption
2 W
Power consumption
4 VA
Manufacturer product status
Commercialized
Compliant with standard(s)
EN 60204-1
EN 62061
EN ISO 13849-1
VDE 0113-1
SIL3 / PL.e / Cat.4
PFH = 2.31E-09
CE
cULus
EAC
TUV
CCC
EN 62061
EN ISO 13849-1
VDE 0113-1
SIL3 / PL.e / Cat.4
PFH = 2.31E-09
CE
cULus
EAC
TUV
CCC
Class
SIL3 / PL.e / Cat.4
Benefits
Positive-guided relay outputs -- 4 safety contacts (N/O); instantaneous
LED display for switch status of the safety contacts
Connection for feedback loop
Operation -- Single-channel
Plug-in connection terminals (either spring-loaded terminal or screw terminal)
The contact expansion module expands an existing circuit.
As the output relays are monitored via the base unit's feedback loop; the safety functions on the existing circuit are transferred to the contact expansion module.
The safety function remains effective in the case of a component failure.
Earth fault in the feedback loop -- Detected; depending on the base unit that is used.
Earth fault in the input circuit -- The output relays de-energize and the safety contacts open.
LED display for switch status of the safety contacts
Connection for feedback loop
Operation -- Single-channel
Plug-in connection terminals (either spring-loaded terminal or screw terminal)
The contact expansion module expands an existing circuit.
As the output relays are monitored via the base unit's feedback loop; the safety functions on the existing circuit are transferred to the contact expansion module.
The safety function remains effective in the case of a component failure.
Earth fault in the feedback loop -- Detected; depending on the base unit that is used.
Earth fault in the input circuit -- The output relays de-energize and the safety contacts open.
Related Documents
Name | Last Update | Language |
---|---|---|
Pilz - PZE X4.1P - Manual.pdf | 14 Oct 2021 | English (US) |