ABB
1SDA063011R1T7S 1600 PR232/P LSI In=1600A 3p F F M (T7MSFC3AC000000XX)
T7S 1600 PR232/P LSI In=1600A 3p F F M (T7MSFC3AC000000XX)
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T7S 1600 PR232/P LSI In=1600A 3p F F M - 3-poles (3P3d) - Rated current 1600A - Short circuit breaking capacity (Icu) 50kA (415Vac) - Electronic (PR232/P LSI) trip unit
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA063011R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Click on the colored tile to view a product selector for this product series:
1SDA063011R1ABB - Tmax T
Description
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T7S 1600 PR232/P LSI In=1600A 3p F F M - 3-poles (3P3d) - Rated current 1600A - Short circuit breaking capacity (Icu) 50kA (415Vac) - Electronic (PR232/P LSI) trip unit
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC)
Sub-range name
T7S complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Poles
3-poles (3P3d)
Rated current
1600A
Trip current rating
1600 AT
Frame current rating
1600 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
750Vdc
Rated voltage (AC)
690Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
85kA (240Vac)
50kA (380Vac)
50kA (415Vac)
50kA (440Vac)
40kA (500Vac)
30kA (690Vac)
50kA (380Vac)
50kA (415Vac)
50kA (440Vac)
40kA (500Vac)
30kA (690Vac)
Short circuit withstand current (Icw)
20kA (1s)
Service short circuit current breaking capacity (Ics)
85kA (240Vac)
50kA (380Vac)
50kA (415Vac)
50kA (440Vac)
40kA (500Vac)
30kA (690Vac)
50kA (380Vac)
50kA (415Vac)
50kA (440Vac)
40kA (500Vac)
30kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(415Vac) 100 %
Trip unit type
Technology = Electronic
Series = PR232/P LSI
Protection = LSI
Display = none
Series = PR232/P LSI
Protection = LSI
Display = none
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (640A...1600A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (960A...16000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1...12 x In (1600A...19200A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (960A...16000A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1...12 x In (1600A...19200A)
Operating mode
Stored energy closing/opening mechanism
Dimensions
H268mm x W210mm x D178mm
Power dissipation/losses
(1-pole) 77 W
Order code / Manufacturer SKU
T7S 1600 PR232/P LSI In=1600A 3p F F M
T7MSFC3AC000000XX
1SDA063011R1
T7MSFC3AC000000XX
1SDA063011R1
Manufacturer product status
Commercialized
EAN code
8015644655600
UNSPSC code
39121616
UPC code
804325535205
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |