ABB
1SDA060315R1T6L630 TMA630-6300 4pFF N100% 1000VAC/DC
T6L630 TMA630-6300 4pFF N100% 1000VAC/DC
Moulded / Molded Case Circuit Breaker (MCCB) - 100% neutral rating - ABB / SACE (Tmax T (IEC) 1000Vac series) - T6L630 TMA630-6300 4pFF N100% 1000VAC/DC - 4-poles (4P4d) - Rated current 630A - Short circuit breaking capacity (Icu) 12kA (1000Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T6L630TMA63063004pFFN1001000VACDC
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA060315R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
1SDA060315R1ABB - Tmax T 1000Vac MCCBs
Description
Moulded / Molded Case Circuit Breaker (MCCB) - 100% neutral rating - ABB / SACE (Tmax T (IEC) 1000Vac series) - T6L630 TMA630-6300 4pFF N100% 1000VAC/DC - 4-poles (4P4d) - Rated current 630A - Short circuit breaking capacity (Icu) 12kA (1000Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T6L630TMA63063004pFFN1001000VACDC
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC) 1000Vac
Sub-range name
T6L complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Design
100% neutral rating
Poles
4-poles (4P4d)
Rated current
630A
Trip current rating
630 AT
Frame current rating
630 AF
Rated operating voltage (Ue)
1000 V
Rated voltage (AC)
1000Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
12kA (1000Vac)
Short circuit withstand current (Icw)
7.6kA (1s)
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = TMA
Display = none
Series = TMA
Display = none
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- adjustable 0.7...1 x In (441A...630A)
Short-circuit pickup current -- adjustable 5...10 x In (3150A...6300A)
Short-circuit pickup current -- adjustable 5...10 x In (3150A...6300A)
Operating mode
Toggle
Dimensions
H268mm x W280mm x D103.5mm
Electrical durability (with load)
7000 operations
Mechanical durability (at no load)
20000 operations
Power dissipation/losses
(1-pole) 30.6 W
Order code / Manufacturer SKU
T6L630 TMA630-6300 4pFF N100% 1000VAC/DC
1SDA060315R1
1SDA060315R1
Manufacturer product status
Commercialized
Equivalent to
T6L630TMA63063004pFFN1001000VACDC
EAN code
8015644627836
UNSPSC code
39121616
UPC code
804325509107
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)