ABB
1SDA054532R1T5V400 TMA400-4000 4pFFC1150VAC/DC N100%
T5V400 TMA400-4000 4pFFC1150VAC/DC N100%
Moulded / Molded Case Circuit Breaker (MCCB) - 100% neutral rating - ABB / SACE (Tmax T (IEC) 1150Vac series) - T5V400 TMA400-4000 4pFFC1150VAC/DC N100% - 4-poles (4P4d) - Rated current 400A - Short circuit breaking capacity (Icu) 12kA (1150Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T5V400TMA40040004pFFC1150VACDCN100
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA054532R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
1SDA054532R1ABB - Tmax T 1150Vac MCCBs
Description
Moulded / Molded Case Circuit Breaker (MCCB) - 100% neutral rating - ABB / SACE (Tmax T (IEC) 1150Vac series) - T5V400 TMA400-4000 4pFFC1150VAC/DC N100% - 4-poles (4P4d) - Rated current 400A - Short circuit breaking capacity (Icu) 12kA (1150Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T5V400TMA40040004pFFC1150VACDCN100
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC) 1150Vac
Sub-range name
T5V complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Design
100% neutral rating
Poles
4-poles (4P4d)
Rated current
400A
Trip current rating
400 AT
Frame current rating
400 AF
Rated operating voltage (Ue)
1150 V
Rated Voltage (DC)
1000Vdc
Rated voltage (AC)
1150Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1150 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
20kA (1000Vac)
12kA (1150Vac)
12kA (1150Vac)
Short circuit withstand current (Icw)
5kA (1s)
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = TMA
Display = none
Series = TMA
Display = none
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- adjustable 0.7...1 x In (280A...400A)
Short-circuit pickup current -- adjustable 5...10 x In (2000A...4000A)
Short-circuit pickup current -- adjustable 5...10 x In (2000A...4000A)
Operating mode
Toggle
Dimensions
H205mm x W184mm x D103.5mm
Electrical durability (with load)
7000 operations
Mechanical durability (at no load)
20000 operations
Power dissipation/losses
(1-pole) 19.5 W
Order code / Manufacturer SKU
T5V400 TMA400-4000 4pFFC1150VAC/DC N100%
1SDA054532R1
1SDA054532R1
Manufacturer product status
Commercialized
Equivalent to
T5V400TMA40040004pFFC1150VACDCN100
EAN code
8015644556334
UNSPSC code
39121616
UPC code
804325531252
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |