ABB
1SDA054469R1T5L 630 TMA 500-5000 3p F F
T5L 630 TMA 500-5000 3p F F
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T5L 630 TMA 500-5000 3p F F - 3-poles (3P3d) - Rated current 500A - Short circuit breaking capacity (Icu) 120kA (415Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T5L630TMA50050003pFF
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA054469R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Click on the colored tile to view a product selector for this product series:
1SDA054469R1ABB - Tmax T
Description
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T5L 630 TMA 500-5000 3p F F - 3-poles (3P3d) - Rated current 500A - Short circuit breaking capacity (Icu) 120kA (415Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T5L630TMA50050003pFF
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC)
Sub-range name
T5L complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Poles
3-poles (3P3d)
Rated current
500A
Trip current rating
500 AT
Frame current rating
630 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
750Vdc
Rated voltage (AC)
690Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
200kA (240Vac)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
85kA (500Vac)
70kA (690Vac)
100kA (250Vdc; 2 poles in series)
70kA (500Vdc; 2-poles in series)
50kA (750Vdc; 3-poles in series)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
85kA (500Vac)
70kA (690Vac)
100kA (250Vdc; 2 poles in series)
70kA (500Vdc; 2-poles in series)
50kA (750Vdc; 3-poles in series)
Short circuit withstand current (Icw)
5kA (1s)
Service short circuit current breaking capacity (Ics)
200kA (240Vac)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
63.75kA (500Vac)
35kA (690Vac)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
63.75kA (500Vac)
35kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(415Vac) 100 %
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = TMA
Display = none
Series = TMA
Display = none
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- adjustable 0.7...1 x In (350A...500A)
Short-circuit pickup current -- adjustable 5...10 x In (2500A...5000A)
Short-circuit pickup current -- adjustable 5...10 x In (2500A...5000A)
Operating mode
Toggle
Dimensions
H205mm x W140mm x D103.5mm
Electrical durability (with load)
5000 operations
Mechanical durability (at no load)
20000 operations
Power dissipation/losses
(1-pole) 28.8 W
Order code / Manufacturer SKU
T5L 630 TMA 500-5000 3p F F
1SDA054469R1
1SDA054469R1
Manufacturer product status
Commercialized
Equivalent to
T5L630TMA50050003pFF
EAN code
8015644555726
UNSPSC code
39121616
UPC code
804325610933
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |