ABB
1SDA054250R1T4V 250 TMA 200-2000 3p F F
T4V 250 TMA 200-2000 3p F F
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T4V 250 TMA 200-2000 3p F F - 3-poles (3P3d) - Rated current 200A - Short circuit breaking capacity (Icu) 200kA (415Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T4V250TMA20020003pFF
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA054250R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Click on the colored tile to view a product selector for this product series:
1SDA054250R1ABB - Tmax T
Description
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T4V 250 TMA 200-2000 3p F F - 3-poles (3P3d) - Rated current 200A - Short circuit breaking capacity (Icu) 200kA (415Vac) - Thermal-Magnetic (adjustable) (TMA) trip unit - equivalent to T4V250TMA20020003pFF
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC)
Sub-range name
T4V complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Poles
3-poles (3P3d)
Rated current
200A
Trip current rating
200 AT
Frame current rating
250 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
750Vdc
Rated voltage (AC)
690Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
200kA (240Vac)
200kA (380Vac)
200kA (415Vac)
180kA (440Vac)
150kA (500Vac)
80kA (690Vac)
100kA (250Vdc; 2 poles in series)
65kA (500Vdc; 2-poles in series)
50kA (750Vdc; 3-poles in series)
200kA (380Vac)
200kA (415Vac)
180kA (440Vac)
150kA (500Vac)
80kA (690Vac)
100kA (250Vdc; 2 poles in series)
65kA (500Vdc; 2-poles in series)
50kA (750Vdc; 3-poles in series)
Service short circuit current breaking capacity (Ics)
200kA (240Vac)
200kA (380Vac)
200kA (415Vac)
180kA (440Vac)
150kA (500Vac)
80kA (690Vac)
200kA (380Vac)
200kA (415Vac)
180kA (440Vac)
150kA (500Vac)
80kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(415Vac) 100 %
Trip unit type
Technology = Thermal-Magnetic (adjustable)
Series = TMA
Display = none
Series = TMA
Display = none
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- adjustable 0.7...1 x In (140A...200A)
Short-circuit pickup current -- adjustable 5...10 x In (1000A...2000A)
Short-circuit pickup current -- adjustable 5...10 x In (1000A...2000A)
Operating mode
Toggle
Dimensions
H205mm x W105mm x D103.5mm
Electrical durability (with load)
8000 operations
Mechanical durability (at no load)
20000 operations
Power dissipation/losses
(1-pole) 9.9 W
Order code / Manufacturer SKU
T4V 250 TMA 200-2000 3p F F
1SDA054250R1
1SDA054250R1
Manufacturer product status
Commercialized
Equivalent to
T4V250TMA20020003pFF
EAN code
8015644553470
UNSPSC code
39121616
UPC code
804325504355
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |