ABB
1SDA054143R1T4L 320 PR222DS/P-LSI In=320 3p F F
T4L 320 PR222DS/P-LSI In=320 3p F F
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T4L 320 PR222DS/P-LSI In=320 3p F F - 3-poles (3P3d) - Rated current 320A - Short circuit breaking capacity (Icu) 120kA (415Vac) - Electronic (PR222DS/P-LSI) trip unit - equivalent to T4L320PR222DSPLSIIn3203pFF
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA054143R1
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Click on the colored tile to view a product selector for this product series:
1SDA054143R1ABB - Tmax T
Description
Moulded / Molded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax T (IEC) series) - T4L 320 PR222DS/P-LSI In=320 3p F F - 3-poles (3P3d) - Rated current 320A - Short circuit breaking capacity (Icu) 120kA (415Vac) - Electronic (PR222DS/P-LSI) trip unit - equivalent to T4L320PR222DSPLSIIn3203pFF
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax T (IEC)
Sub-range name
T4L complete breakers
Functions
Moulded / Molded Case Circuit Breaker (MCCB)
Protection parameters set (available via Modbus)
Protections (L/S/I/G) (available via Modbus)
Failed tripping under fault conditions (available via Modbus)
Protection parameters set (available via Modbus)
Protections (L/S/I/G) (available via Modbus)
Failed tripping under fault conditions (available via Modbus)
Poles
3-poles (3P3d)
Rated current
320A
Trip current rating
320 AT
Frame current rating
320 AF
Rated operating voltage (Ue)
690 V
Rated Voltage (DC)
750Vdc
Rated voltage (AC)
690Vac
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Ring-lug or bar connections
Ultimate short circuit current breaking capacity (Icu)
200kA (240Vac)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
85kA (500Vac)
70kA (690Vac)
100kA (250Vdc; 2 poles in series)
70kA (500Vdc; 2-poles in series)
50kA (750Vdc; 3-poles in series)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
85kA (500Vac)
70kA (690Vac)
100kA (250Vdc; 2 poles in series)
70kA (500Vdc; 2-poles in series)
50kA (750Vdc; 3-poles in series)
Service short circuit current breaking capacity (Ics)
200kA (240Vac)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
85kA (500Vac)
70kA (690Vac)
120kA (380Vac)
120kA (415Vac)
100kA (440Vac)
85kA (500Vac)
70kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(415Vac) 100 %
Trip unit type
Technology = Electronic
Series = PR222DS/P-LSI
Protection = LSI
Display = none
Series = PR222DS/P-LSI
Protection = LSI
Display = none
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
(S) Protection against short-circuit with time delay
(I) Instantaneous protection against short-circuit
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (128A...320A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (192A...3200A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...12 x In (480A...3840A)
S - Protection against short-circuit with time delay -- adjustable 0.6...10 x In (192A...3200A); with adjustable time trip curve
I - Instantaneous protection against short-circuit -- adjustable 1.5...12 x In (480A...3840A)
Measurement function
Phase currents
Operating mode
Toggle
Dimensions
H205mm x W105mm x D103.5mm
Electrical durability (with load)
6000 operations
Mechanical durability (at no load)
20000 operations
Power dissipation/losses
(1-pole) 17.6 W
Order code / Manufacturer SKU
T4L 320 PR222DS/P-LSI In=320 3p F F
1SDA054143R1
1SDA054143R1
Manufacturer product status
Commercialized
Equivalent to
T4L320PR222DSPLSIIn3203pFF
EAN code
8015644552053
UPC code
804325616379
UNSPSC code
39121616
Compliant with standard(s)
IEC 60947-2
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
EC directive "Low Voltage Directives" (LVD) no. 2006/95/CE (in replacement of 73/23/ CEE and subsequent amendments)
EC directive "Electromagnetic Compatibility Directive" (EMC) 2004/108/CE
IEC 60073
IEC 60417-2
IEC 60529
IEC 60068-2-30 (tropicalization)
IEC 60068-2-6 (resistance to shocks and vibrations)
IEC 60068-2-27 (resistance to shocks)
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Tmax T Moulded Case Circuit Breakers - Catalogue.pdf | 02 Feb 2023 | English (US) |