ABB
1SAZ711201R1021T16-0.74
T16-0.74
Thermal overload protection relay (TOR) - ABB (T16 series) - T16-0.74 - rated current 0.55A...0.74A (adjustable) - 120W (400/415Vac) - Manual or automatic reset operation - Direct mounting on cont. (45mm width) - 1NO+1NC aux. contacts - direct connection to contact. (ingoing)
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SAZ711201R1021
Online Price
$65.89
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
ABB - T16 series thermal overload relays1SAZ711201R1021
Description
Thermal overload protection relay (TOR) - ABB (T16 series) - T16-0.74 - rated current 0.55A...0.74A (adjustable) - 120W (400/415Vac) - Manual or automatic reset operation - Direct mounting on cont. (45mm width) - 1NO+1NC aux. contacts - direct connection to contact. (ingoing)
Specifications
Primary brand
ABB
Main function
Thermal Overload Relay (TOR)
Product series / family name
T16 series
Network frequency
50/60 Hz
Functions
Thermal overload protection relay (TOR)
Manual / automatic reset function
Test trip function
Stop function
Rotary knob for adjusting rated motor current
Manual / automatic reset function
Test trip function
Stop function
Rotary knob for adjusting rated motor current
Design
bimetallic tripping elements
Poles
3-poles (3P)
Rated current
0.55A...0.74A (adjustable)
Rated active power (kW)
120W (400/415Vac)
Rated operating voltage (Ue)
690 V
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
690 V
Connection type
direct connection to contact. (ingoing)
Screw-clamp connections (outgoing)
Screw-clamp connections (outgoing)
Protection functions
3-phase overload
Phase loss
Thermal overload Class 10
Phase loss
Thermal overload Class 10
Protection settings
Thermal protection (Overload) -- 0.55A...0.74A (adjustable)
Net Height (mm)
76.7 mm
Net Width (mm)
45 mm
Net Depth (mm)
53.5 mm
Mounting mode
Direct mounting on cont.
Operating mode
Manual or automatic reset
Contacts type
1NO+1NC aux. contacts
Ambient air temperature for operation
-25...+60 °C
Visual position indicator
Trip indication on the front
Technical compatibility with
Suitable for 3-phase and single-phase applications
B6 series contactors
B7 series contactors
AS09-AS16 series contactors
B6 series contactors
B7 series contactors
AS09-AS16 series contactors
Customs Tariff Number
85364900
Minimum current
0.55 A
Maximum current
0.74 A
Power dissipation/losses
at rated operating conditions per pole 1.1W...2 W
Order code / Manufacturer SKU
T16-0.74
Manufacturer product status
Commercialized
EAN code
4013614397868
Compliant with standard(s)
IEC /EN60947-4-1
IEC /EN60947-1
IEC /EN60947-5-1
UL508
CSA22.2 No.14
UL 60947-1
UL60947-4-1
IEC /EN60947-1
IEC /EN60947-5-1
UL508
CSA22.2 No.14
UL 60947-1
UL60947-4-1
Class
10
Operating rate
15 Cycles/hour
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|