ABB
1SAZ431201R1002TF140DU-110
TF140DU-110
Thermal overload protection relay (TOR) - ABB (TF140DU series) - TF140DU-110 - rated current 80A...110A (adjustable) - 55kW (400/415Vac) - Direct mounting on cont. (89mm width) - 1NO+1NC aux. contacts - direct connection to contact. (ingoing)
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SAZ431201R1002
Online Price
$343.12
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
ABB - TF140DU series thermal overload relays1SAZ431201R1002
Description
Thermal overload protection relay (TOR) - ABB (TF140DU series) - TF140DU-110 - rated current 80A...110A (adjustable) - 55kW (400/415Vac) - Direct mounting on cont. (89mm width) - 1NO+1NC aux. contacts - direct connection to contact. (ingoing)
Specifications
Primary brand
ABB
Main function
Thermal Overload Relay (TOR)
Product series / family name
TF140DU series
Network frequency
DC or 50/60 Hz
Functions
Thermal overload protection relay (TOR)
Manual / automatic reset function
Test trip function
Stop function
Rotary knob for adjusting rated motor current
Manual / automatic reset function
Test trip function
Stop function
Rotary knob for adjusting rated motor current
Design
bimetallic tripping elements
Poles
3-poles (3P)
Rated current
80A...110A (adjustable)
Rated active power (kW)
55kW (400/415Vac)
Rated operating voltage (Ue)
(IEC) 690 V
(UL/CSA) 600 V
(UL/CSA) 600 V
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
690 V
Connection type
direct connection to contact. (ingoing)
Screw-clamp connections (outgoing)
Screw-clamp connections (outgoing)
Protection functions
3-phase overload
Phase loss
Thermal overload Class 10A
Phase loss
Thermal overload Class 10A
Protection settings
Thermal protection (Overload) -- 80A...110A (adjustable)
Mounting mode
Direct mounting on cont.
Contacts type
1NO+1NC aux. contacts
Net Height (mm)
140 mm
Net Width (mm)
89 mm
Net Depth (mm)
126 mm
Ambient air temperature for operation
-25...+55 °C
Visual position indicator
Trip indication on the front
Technical compatibility with
Suitable for 3-phase / single-phase / DC applications
AF116 / AF140 series contactors
AF116 / AF140 series contactors
Customs Tariff Number
85364900
Minimum current
80 A
Maximum current
110 A
Power dissipation/losses
at rated operating conditions per pole 2.1 W
Order code / Manufacturer SKU
TF140DU-110
Manufacturer product status
Commercialized
EAN code
4013614446825
Compliant with standard(s)
IEC /EN60947-4-1
IEC /EN60947-1
IEC /EN60947-5-1
UL508
CSA22.2 No.14
UL 60947-1
UL60947-4-1
IEC /EN60947-1
IEC /EN60947-5-1
UL508
CSA22.2 No.14
UL 60947-1
UL60947-4-1
Class
10A
Operating rate
15 Cycles/hour
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Motor protection and control - Catalogue 2020.pdf | 22 Aug 2022 | English (US) |